FIRE DAMPER CONTROLLER

SPECIFICATIONS :

SYSTEM SUPPLY :

230VAC ±10%, 50Hz.

• LED INDICATIONS :

INTRSUCTION FOR SETTINGS THE PANEL:

  1. TEST  : If this key pressed then Damper  power gets cut It means using  this Test  Key we can cross check damper  open/Closed Operation by cut  off the  power  of damper.

          To indicate whether controller works in normal mode or Test                       mode

          HEALTHY LED given,

          If HEALTHY LED STEADY ON: TEST  MODE

          If HEALTHY LED BLINK: NORMAL  MODE

  1. RESET : This key is used to go to Normal mode from test mode And HEALTY LED BLINK means Normal
  2. LTY LED BLINK means Normal

TERMINAL DETAILS:

TYPE 1:

Power Supply 230VC Input power to Damper Damper 1 Supply Damper 2 Supply BMS 1 Contact BMS 2 Contact DP 1 Feedback DP 2 Feedback FIRE INPUT
L
N
*
*
*
*
*
*
C
NO
C
NO
11
12
13
14
15
16

TYPE 2:

Power Supply 230VC Damper 1 Supply Damper 2 Supply BMS 1 Contact BMS 2 Contact DP 1 Feedback DP 2 Feedback FIRE INPUT
L
N
C
NO
C
NO
C
NO
C
NO
11
12
13
14
15
16
  • Power Supply: It is 230VAC Auxiliary power for Fire damper
  • Input power to Damper: Here we can give 230VAC or 24VDC as per Damper specification.
  • Damper 1 Supply / Damper 2 Supply:

                       

                 Type 1: Whatever given to Input power to Damper will acts                        as  damper 1 / damper 2 Supply. This supply gets cut off if                      Fire Input Signal.

                 Type 2: It is potential free C, NO contact for power supply of                   Damper.

  • BMS 1 Contact: It is potential free C, NO contact for BMS communication which indicates Damper 1 Open/Close.
  • BMS 2 Contact: It is potential free C, NO contact for BMS communication which indicates Damper 2 Open/Close.
  • DP1 Feedback: It is feedback signal come from Damper 1 which sense whether damper1 Open/Closed.
  • DP2 Feedback: It is feedback signal come from Damper 2 which sense whether damper2 Open/Closed.
  • FIRE INPUT: It is input signal which sense FIRE, if fire signal then Power to the Damper1 and Damper 2 gets cutoff by

AUTOMATION PHILOSOPHY:

The Fire Damper Controller sense two (2) damper feedback digital inputs and one Fire input, accordingly Damper LED and BMS1/BMS2 contacts gets ON/OFF. It give Fire alarm indication if Fire sensed and turn OFF Damper power supply.

Manufactured by

AIRCON CONTROLS

Office & Work :

Sector 15, Sahyandry Residency, beside Balaji traders, Ambegaon Pathar,Pune -411046.

Mobile :

+91-9822032986 , +91-9763444007

E-mail

tushar.aircon@gmail.com , vip.adhau@gmail.com

QUICK ENQUIRY

Please enable JavaScript in your browser to complete this form.

Quick Enquiry