Aircon Controls

3 A/C CONTROLLER ( Model:- AC_3TT-V1 )

SILENT FEATURES

TECHNICAL SPECIFICATIONS

SYSTEM SUPPLY :

230 VAC +/- 15%

OUTPUT CONTACT RATING:

Output contact rating for AC1, AC2 ,AC3 is 30 A at

250 VAC & for ALARM is 7 A at 250 V AC

POWER ON DELAY TIME :

A/C 1 30 SEC., A/C2 60 SEC, A/C3 90 SEC.

ROOM TEMP. SET POINTS :

 A/C 1 cut in 22°C cut off 19°C user settable.

A/C 2 cut in 24°C cut off 21°C user settable. A/C 3 cut in 26°C cut off 23°C user settable.

CYCLE TIME :

DIMENSIONS :

215 x 195 x 70 mm

DISPLAY :

Running Mode: Display show

A. Balance Cycle Time

B. Room Temperature.

C. Actual Voltage

D. Fault message if any

INDICATIONS :

AC 1 On / AC 2 On / AC 3 On / Healthy / Fault Indication

AUTO / MANUAL Switch :

For AC1 / AC2 / AC

WORKING :

In normal working conditions when power is turned ON. Display will show Cycle Time, Room temperature. Now depending on the Room temperature & Room temp. set points of A/C1,A/C2,A/C3 , they will be turned ON after their respective power on delay & this condition system makes ON/OFF of A/Cs depending on the set point of Temperature & Cycle time in tens of minutes. If room temperature exceeds the set point of HIGH TEMP, ALARM RELAY contacts get closed.

To view/change set points of A/C1 Cut In, A/C2 Cut In, A/C3 Cut In, High temperature & Change over cycle time in tens of minutes press SET key.

PARAMETER SET POINTS :

  1. Cycle
  2. AC 1 ON set point
  3. AC 2 ON set point
  4. AC 3 ON set point
  5. Hysteresis
  6. Room High
  7. Hysteresis
  8. Room Low
  9. Hysteresis
  10. Under Voltage
  11. Over Voltage

Optional Features :- BMS Compatibility MODBUS PROTOCOL & Volt free fire Contact to protect against fire input.

NOTE :- If require any help at time of setting please call 9822032986